EX Dual Fuel Steam Boilers

The Miura EX Gas/Oil Series Industrial Steam Boiler is the most versatile industrial steam boiler in the world.

The Miura EX Series steam boilers, with gas and oil fuel options, are ideal for hospitals and other facilities that are required to have a secondary fuel source.

The EX steam boiler uses our floating header design on an upright drum-shaped pressure vessel. With a single button, the Miura EX-Series boiler a from a cold start to full steam output in less than 5 minutes. These quick start-up benefits enable many industries to consume less fuel and boiler water, reducing emissions and operating cost.

  • Dual fuel: Natural Gas, Propane or #2 Fuel Oil
  • High-pressure available (300 MAWP, 250 MAWP or 170 MAWP)
  • NOx rating is available as low as 30ppm depending on model
  • Quick start up in just 5 minutes
  • Occupies 33% less floor space than typical firetube boilers
  • Equipped with an early warning scale monitor
The Miura EX Gas/Oil Series Industrial Steam Boiler is the most versatile industrial steam boiler in the world.
Features

The unique compact design of the Miura EX Series steam boiler uses a low water volume pressure vessel offering high output capacities to meet your facilities demands. The reduced boiler footprint provides design flexibility, reduced construction cost, and better utilization of existing space to increase steam capabilities. The “brain” of the EX-Series, the BL Controller, provides online boiler monitoring  and measuring capabilities on an easy-to-read LCD display and enhances boiler maintenance procedures with data-driven alerts. The BL Controller monitors:

  • Steam Pressure
  • Flue Gas Temperature
  • Feed Water Temperature
  • Scale Monitor Temperature
  • Overheat Monitor Temperature
  • Flame Current
  • Remaining Time to Blowdown
  • Water Conductivity
  • Plus much more!
Features

Contact a Miura Rep

Learn more about our EX boilers.

Standard Pressure
 
 
Utilization Horsepower
Maximum Pressure [1]
Equivalent Output [2]
Heat Output
Efficiency (fuel to stream) [3]
Operational Weight
Operational Water Content
Shipping Weight
Width
Length
Height
Power Supply
Fuel Type [4]
No. 2 Oil
Gas Supply Pressure
Chimney Diameter (ID)
UNIT
 
BHP
PSIG
LB/HR
MMBTU/HR
 
LBS
 
LBS
IN.
IN.
IN.
 
 
GAL/HR
PSIG
IN.
EX-100-07
 
100
170
3,450
3.348
85%
5,900
65
4,600
80 1/8"
108 1/2"
98 7/8"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
27.5
3-5 PSIG
14" OD
EX-150-07
 
150
170
5,175
5.022
85%
9,600
90
7,800
68 1/2"
130"
119 5/8"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
41.2
3-5 PSIG
20" OD
EX-200-07
 
200
170
6,900
6.695
85%
9,600
90
7,800
68 1/2"
130"
119 5/8"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
55
3-5 PSIG
20" OD
EX-250-07
 
250
170
8,625
8.369
85%
9,900
110
8,000
68 1/2"
135 1/8"
145 1/4"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
68,7
3-5 PSIG
20" OD
EX-300-07
 
300
170
10,350
10.043
85%
13,500
135
11,200
76 3/4"
141 3/4"
156 1/8"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
85.5
3-5 PSIG
26" OD
Note 1: Optional EXH-SGO Series at 250 Psig MAWP, 225 Psig maximum operating.
Note 2: Equivalent output calculated from and at 212ºF (100ºC) feed water at 212ºF (100ºC) steam.
Note 3: Thermal effieciencies are based on high heating values of fuels at 68ºF (20ºC) feed water.
Note 4: UL and c-UL approved for natural gas or propane.
Low Nox Burner with FGR
 
 
Utilization Horsepower
Maximum Pressure [1]
Equivalent Output [2]
Heat Output
Efficiency (fuel to stream) [3]
Operational Weight
Operational Water Content
Shipping Weight
Width
Length
Height
Power Supply
Fuel Type [4]
No. 2 Oil
Gas Supply Pressure
Chimney Diameter (ID)
UNIT
 
BHP
PSIG
LB/HR
MMBTU/HR
 
LBS
 
LBS
IN.
IN.
IN.
 
 
GAL/HR
PSIG
IN.
EXN-250-07
 
250
170
8,625
8.369
85%
13,700
135
11,200
76 3/4"
140 1/2"
156 1/8"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
68.7
3-5 PSIG
26" OD
EXN-300-07
 
300
170
10,350
10.043
85%
13,700
135
11,200
76 3/4"
140 1/2"
156 1/8"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
82.5
3-5 PSIG
26" OD
Note 1: Optional EXH-SGO Series at 250 Psig MAWP, 225 Psig maximum operating.
Note 2: Equivalent output calculated from and at 212ºF (100ºC) feed water at 212ºF (100ºC) steam.
Note 3: Thermal effieciencies are based on high heating values of fuels at 68ºF (20ºC) feed water.
Note 4: UL and c-UL approved for natural gas or propane.
High Pressure
 
 
Utilization Horsepower
Maximum Pressure [1]
Equivalent Output [2]
Heat Output
Efficiency (fuel to stream) [3]
Operational Weight
Operational Water Content
Shipping Weight
Width
Length
Height
Power Supply
Fuel Type [4]
No. 2 Oil
Gas Supply Pressure
Chimney Diameter (ID)
UNIT
 
BHP
PSIG
LB/HR
MMBTU/HR
 
LBS
 
LBS
IN.
IN.
IN.
 
 
GAL/HR
PSIG
IN.
EXH-200-07
 
170 - 270
300
6,900
6.695
84%
10,500
95
8,500
68 1/2"
130"
119 5/8"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
55.6
3-5 PSIG
20" OD
EXH-300-07
 
300
300
10,350
10.043
84%
15,100
140
12,400
76 3/4"
141 3/4"
156 1/8"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
83.4
3-5 PSIG
26" OD
Note 1: Optional EXH-SGO Series at 250 Psig MAWP, 225 Psig maximum operating.
Note 2: Equivalent output calculated from and at 212ºF (100ºC) feed water at 212ºF (100ºC) steam.
Note 3: Thermal effieciencies are based on high heating values of fuels at 68ºF (20ºC) feed water.
Note 4: UL and c-UL approved for natural gas or propane.
High Pressure / Low Nox Burner with FGR
 
 
Utilization Horsepower
Maximum Pressure [1]
Equivalent Output [2]
Heat Output
Efficiency (fuel to stream) [3]
Operational Weight
Operational Water Content
Shipping Weight
Width
Length
Height
Power Supply
Fuel Type [4]
No. 2 Oil
Gas Supply Pressure
Chimney Diameter (ID)
UNIT
 
BHP
PSIG
LB/HR
MMBTU/HR
 
LBS
 
LBS
IN.
IN.
IN.
 
 
GAL/HR
PSIG
IN.
EXNH-300-07
 
300
300
10,350
10.043
84%
15,300
40
12,400
76 3/4"
141 3/4"
156 1/8"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
83.4
3-5 PSIG
26" OD
EXNH-250-07
 
250
250
8,265
8.369
84%
15,300
140
12,400
76 3/4"
141 3/4"
156 1/8"
575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
Natural Gas, Propane, No. 2 Oil
69.5
3-5 PSIG
26" OD
Note 1: Optional EXH-SGO Series at 250 Psig MAWP, 225 Psig maximum operating.
Note 2: Equivalent output calculated from and at 212ºF (100ºC) feed water at 212ºF (100ºC) steam.
Note 3: Thermal effieciencies are based on high heating values of fuels at 68ºF (20ºC) feed water.
Note 4: UL and c-UL approved for natural gas or propane.