Split Flow

Quality brine is supplied throughout
the entire resin layer so ideal
regeneration is performed every cycle
Conventional Parallel Water Flow
(while regenerating)

As brine circulates from top to bottom,
it absorbs the hardness released from
the resin, but does not fully regenerate
the bottom portion of the layer.
Utilize “Smart” Water Softener System for Optimized
Boiler Operation
The MW will automatically engage a 24 hour regeneration for each tank in the event the integral water totalizer is compromised. (Connection from a makeup water solenoid valve is required).
If Colormetry detects hardness leakage, it sends a signal to the boiler's hardness alarm contactor, and will automatically switch tanks to continue to supply softened water. The control system interfaces with the boiler controller to initiate automatic blowdown after receiving hardness alarms.
Monitoring the brine flow rate with a flow meter at the brine input line, the MW prevents hardness leakage by managing regeneration of the brine amount and detecting brine introduction failure.
A brine concentration sensor monitors the specific gravity of the brine, detecting the status of the regenerating salt and preventing regeneration failure in the event the tank is allowed to run empty.
Colormetry* (CMU-224H Hardness)
Water hardness is a common cause of boiler
damage. Typically, water-hardness levels are
checked manually through the use of chemical
reagents. Such measurements are timeconsuming and can result in incorrect readings.
Colormetry solves all these problems by
offering automated reagent injection, mixing
and evaluation integrated into the boiler
control system.
- Automatically monitors water quality
- Controls MW regeneration if hardness is detected
- Alarm and fault history logging
- One-touch reagent replacement
- Compact design
Remote Dashboard Monitoring

The MW system is fully compatible with
Miura's PC dashboard monitoring systems, as
well as third-party PLC integration (Modbus
& BACnet), to further enhance oversight of
softener performance. Integrating the softener
system into the comprehensive boiler controls/
monitoring system maximizes operational
awareness and provides real-time boiler water
quality management, acknowledging its role in
supporting overall system optimization. |