LX-150 SG Print E-mail

LX Gas/Low NOx Series
Low and High Pressure Steam Boiler

Miura’s Ultra Low NOx Steam Generator uses the most advanced technology. The flat shaped burner and the rectangular shaped boiler vessel are uniquely designed for the reliable low NOx.

  • 5 minutes from cold start to full pressure.
  • Ultra Low NOx gas burner with “Quenched flame”.
  • Up to 300HP per boiler and up to 4,500HP (150,000lb/hr) with our MI-system.
  • 170 PSIG and 15 PSIG MAWP available.

MIURA’s exclusive “low water content, water tube” design is the most versatile boiler available in the marketplace today. A once-through, forced circulation steam boiler producing steam in just 5 minutes while maintaining an 85% fuel-to-steam efficiency.

SpecificationsDimensions and Schematic Note
Specifications
LX-150 SG
Utilization Horsepower (*1) 150HP
Maximum Pressure 170 psig MAWP
Equivalent Output
(*2)
5,175 LB/HR
Heat Output 5,022,000 BTU/HR
Efficiency
(fuel to steam)
(*3)
85% (80% without Economizer)
Heating Surface Area 388.2 FT²
Operational Weight 8,620 LBS
Shipping Weight 7,820 LBS
Dimensions Given are Approximate
Width 42.5 in.
Length 141.5 in.
Height 116.5 in.
Combustion System Proprietary Forced Draft, Step Fired Modulation Hi-Low-Off
Ignition System Electric Spark Ignited, Interrupted Gas Pilot
Power Supply 208, 230, 460, 575V, 3 phase, 60Hz
Max. Electrical Consumption 22.1 KVA
Fuel Type (*4) Natural Gas or Propane (3-5 PSIG)
Gas Consumption (*5) 5,880 SCFH
Gas Supply Pressure

3-5 PSIG Natural Gas or Propane

Main Steam Outlet Valve 3 in. (8 in.)
Safety Valve Outlet One 2 1⁄2 in.
Main Water Inlet 1 in.
Fuel Gas Inlet 2 in.
Automatic Surface Blowdown One 3⁄8 in.
Manual Blowdown Two 1 in.
Chimney Diameter (ID) 20 in.
Flame Detector Ultraviolet Flame Eye Sensor
Pressure Control Adjustable Pressure Transducer and Switch
Liquid Volume Control Electric Conductivity Type
Overheat Protection Low Water Cut Off & Thermocouple
 