Multiple water tube, Hot-water boiler. Miura’s Gas/Oil hot-water boiler is a low water content, water tube design, which provides full output within 5 minutes.
Gas/Oil dual fuel burner
Up to 300 BHP per boiler
SpecificationsNote
Specifications
EXW-100 GO
Boiler Type
Natural Gas, Propane, or #2 Oil Fired
Utilization Horsepower
100 BHP
Maximum Pressure
160 PSIG
Heat Output
3,348,000 BTU/HR
Efficiency
80% Gas / 82% Oil
Heating Surface Area
193 FT²
Operational Weight
5,400 LBS
Shipping Weight
4,700 LBS
Width
82 in.
Length
93 in.
Height
99 in.
Combustion System
Proprietary Forced Draft
Ignition System
Electric Spark Ignited, Interrupted Gas Pilot
Power Supply
230, 460, or 575 V, 3 PHASE, 60 HZ
Max. Electrical Consumption
14 KVA
Fuel Type
Natural Gas or Propane (3-5 PSIG) or No. 2 Oil
Gas Consumption
4,185 SCFH
Gas Supply Pressure
3-5 PSIG Natural Gas or Propane
Main Water Outlet
4 in.
Safety Valve Outlet
2 in.
Main Water Inlet
4 in.
Fuel Gas Inlet
2 in.
Manual Blowdown
1 in.
Chimney Diameter (ID)
14 in.
Flame Detector
Ultraviolet Flame Eye Sensor
Overheat Protection
Low Water Cut Off & Flow Switch
Max. Water Temperature
250°F
Full Water Content
85.5 GAL
Temperature Control
Adjustable Temperature Controllers
No. 2 Oil
29.2 GAL/HR
Fuel Oil Inlet
3⁄4 in.
Note
Thermal efficiencies are based on high heating values of fuels at 140°F supply temperature water.
UL and c-UL approved for natural gas and propane.
Gas consumption based on natural gas with high heating value of 1004 BTU/SCF.
All MIURA hot water boilers are fully packaged and test fired at the factory.
Built to meet or exceed UL and ASME standards in U.S.A.; c-UL and B-51 standards in Canada.