Control Panels
Easy-to-see operation and emergency lights:
 |
Green (normal) |
 |
Yellow (warning) |
 |
Red (emergency) |

2 push buttons and a scroll selector only
 |
One push button to start |
 |
Rotary selector switch to modify setting |
Examples
It gives you following information to help the operator to maintain the boiler at good conditions or to solve the problems it may have:
- 52* alarms in plain English (17 with XJ-1)
- 37* warning messages in plain English (10 with XJ-1)
- possible cause or the solution to the problem related to each alarms and warnings.
*The number of alarms and warnings may change without notice
Example (alarm history):
HI FIRE 11,08:30 BURNER ALARM 5 |
|
|
|
|
NO FUEL OR UVSENSOR ERROR |
|
Some alarms and warnings are added
Example:
Feed water temperature increase
Feed water pump time increase
Some alarms and warnings are divided to give more detailed information
Example:
12 Alarms and 6 Warnings for water level probe problem
|
|
M or S PROBE ON & L PROBE OFF |
|
|
|
When is there is no back up probe D
|
|
L, M= ON & S=OFF EXCESSS FEED TIME |
|
|
|
When is there is no back up probe D
Efficiency
The new controller makes the boiler more efficient by:
- Setting the pre-purge timing optimum to the boiler
Honeywell: standard 10s, IRI 30s
New controller standard 10s, IRI 20s
- Purge Cancel function∗ ignores the post purge when fast restart required. It eliminates the loss and shorten response.
∗This function is not set as default
When restart requirement occur during the post-purge, boiler consider post-purge time as pre-purge and shorten the pre-purge timing. It eliminates the loss and shortens response.